UGH017/0500 Series 1 Portable Chillers, PLC Control
OPERATION 4-7
Verify that the readings each screen displays are the ones
you want. You cannot change the readings of the screens
from the Status screens. You can change to status of:
Setpoint temperature
Percent Ethylene Glycol by volume
by going to the Setup screens. You can not change the
other readings; they are read-only screens, reporting envi-
ronmental conditions.
Press the Escape/Previous button at any time
to return to the main screen.
Ref Suction Pressure
70 PSIG
Ref Discharge Pressure
250 PSIG
Refrigerant Discharge pressure - View the status of
the refrigerant discharge pressure in PSIG. Typical dis-
charge pressure is between 190 PSIG and 325 PSIG.
% E.G. BY VOL 0
LOW TEMP CUTOUT 40 F
VIEWING
CHILLER
STATUS
CONTD
Percent Ethylene Glycol by Volume and Low tem-
perature Cutout - displays the percentage of ethylene
glycol or propylene glycol solution (by volume) in the
chiller in degrees Fahrenheit. Changing the percent glycol
automatically changes the low temperature cutout.
Refrigerant suction pressure - shows the status of the
refrigerant suction pressure in PSIG. NOTE: Typical
refrigerant suction pressure is between 55 PSIG and 95
PSIG.