28
ElectricalPhaseErrorLED
TheElectricalPhaseErrorLEDflashesredwhenalinevoltageproblemexists.Thiserror
indicatesalossofphase,phasereversal,orphaseimbalance.
LowFlowLED
TheNoFlowLEDwillbeilluminatediftheflowthroughthechillerisbelowthepreset
acceptablelevel.WhentheStartbuttonisdepressed,thissafetyisdefeatedforaperiodof5
secondsinorderforthepumptoestablishflow.Thissafetywillshutoffthepumpandthe
compressor.IfthechillerhasbeenshutdownbytheNoFlowsafety,theStartbuttonmustbe
depressedinordertorestartthepumpandresetthe5secondtimedelay.
FreezestatLED
IfthecoolanttemperaturebeingdeliveredtotheprocessdropsbelowtheFreezestatLimit
(FLS)setting,thecompressorwillshutoff,thepumpwillremainrunning,andtheFreezestat
LEDwillbeilluminated.TheFreezestatLimitshouldbeset10°F(5°C)abovethefreezingpoint
oftheglycolsolutionand10°F(5°C)belowtheminimum operatingtemperature.TheFreezestat
isfactorysetat38°F(3°C).InordertoresettheFreezestatfaultpresstheAlarmResetbutton
afterthetemperaturehasrisen5°F(3°C)abovetheFreezestatLimit.SeetheProgramMenu
sectionforinstructionsonhowtoadjustFLS.
LowReservoirLevelLED
Whenthewaterlevelinthereservoirdropsbelowthelowerlimitofthefloatswitch,theLow
WaterLevelLEDisilluminatedandthepumpwillshutoff.
CompressorRecycleLED
Thenumberofcompressorstartupsperhourislimitedinordertomaximizecompressor
lifetimeandensureproperreturnofoiltothecompressorcrankcase.Thislightisilluminated
yellowwheneverthereisawaitperiodbeforethecompressorcanbestarted.
HighRefrigerantPressureLED
Ifthecompressordischargerefrigerantpressureexceedsthesettingonthehighrefrigerant
pressuresafety,thecompressorandpumpwillshutoffandtheHighRefrigerantPressureLED
willbeilluminated.PressingtheAlarmResetbuttonwillresettheHighRefrigerantPressure
fault,aslongastheHighRefrigerantPressureswitchlocatedatthedischargeofthecompressor
hasbeenmanuallyreset.