53
Problem PossibleCause Solution
Erratictemperature
control
Lowcoolantflowthroughevaporator Adjustflowtoproperlevel
Intermittentoverloadingofchillercapacity Checktomakesurechillerisproperlysized
forprocessload
Hotgasbypassvalve Contactrefrigerationservicetechnician
Temperaturesensor Replaceiffaulty
Insufficientcooling
(temperature
continuestorise
abovesetpoint)
Processloadtoohigh Checktomakesurechillerisproperlysized
forprocessload
Coolantflowthrough evaporatortoohighorlow Adjustflowtoproperlevel
Insufficientcondensercooling See“HighRefrigerantPressure”
Hotgasbypassvalvestuckopen Contactrefrigerationservicetechnician
Refrigerationcircuitproblem Contactrefrigerationservicetechnician
Temperaturesensor Replaceiffaulty
Drawings
Wehavepreparedacustomsetofdrawingsforyourunitandplacedtheminsidethecontrol
panelpriortoshipment.Pleaserefertothesedrawingswhentroubleshooting,servicing,and
installingtheunit.Ifyoucannotfindthesedrawingsorwishtohaveadditional copies,please
contactourServiceDepartmentandreferencetheserialnumberofyourunit.
ContactConairPartsandServiceat18004581960(intheUnitedStates)or18144376861
(international).Press1forServiceand2forParts.
